IONIFLASH  PERFORMANCES  

Radius of protection of the IONIFLASH air terminal
The radius of protection of an E. S. E. air terminal depends on its height (h) in relation to the surface to be protected, its early streamer emission time and the level of protection chosen.

for
For the graphic method is used, with the abacuses 2.2.3.3. a, b and c of the NF C 17-102 standard.
: protection radius
: height of the point of the E. S. E. air terminal in relation to the horizontal point passing through the top of the element to be protected.
D : 20 m for protection level I
  45 m for protection level II
  60 m for protection level III

: early streamer emission time from the evaluation tests of the 
E. S. E. air terminal.

D(m)  : striking distance or fictitious sphere radius

Protected area
The protected area is delimited by the revolution enclosure of the same axis as the E. S. E. air terminal and defined by the protection radius corresponding to the different heights h considered ( see diagram below):

 

 

 

Radius of protection in meters

h (m) Level 1 * Level 2 * Level 3 *
2 32 40 44
3 48 59 65
4 65 78 86
5 79 97 107
6 79 97 107
8 79 98 108
10 79 99 109
20 80 102 113
40 77 105 118
60 69 104 120

* The protection level is determined up to NF C 17-102 standard (enclosure B)

hn : height of the point of the E. S. E. air terminal in relation to the horizontal plane passing through the top of the element to be protected.
RPn : radius of protection of the E. S. E. air terminal for the height under consideration.